D8 Series User’s Guide
Chapter 5: Tuning and Control
92
General PID Constants by Application
This section gives PID values for many applications. They are useful as control values or as starting
points for PID tuning.
Proportional Band Only (P)
• Set the proportional band to seven percent of the set point.
(Example: Set point = 450, proportional band = 31).
Proportional with Integral (PI)
• Set the proportional band to ten percent of set point.
(Example: Set point = 450, proportional band = 45).
• Set integral to 60.
• Set derivative off.
• Set the output filter to 2.
Proportional and Integral with Derivative (PID)
• Set the proportional band to ten percent of the set point.
(Example: Set point = 450, proportional band = 45).
• Set the integral to 60.
• Set the derivative to 15 percent of the integral.
(Example: Integral = 60, derivative = 9).
• Set the output filter to 2.
Table 5.4 shows general PID constants by application.
Table 5.4
– General PID Constants
APPLICATION
PROPOTIONAL
BAND
INTEGRAL DERIVATIVE
FILTER
OUTPUT
TYPE
CYCLE
TIME
ACTION
Electrical heat with
solid state relays
50°
60
15
4
DZC
–
Reverse
Electrical heat with
electromechanical
relays
50°
60
15
6
TP
20
Reverse
Cool with
solenoid valve
70°
500
90
4
TP
10
Direct
Cool with fans
10°
Off
10
4
TP
10
Direct
Electric heat with
open heat coils
30°
20
Off
4
DZC
–
Reverse
Gas heat with
motorized valves
60°
120
25
8
Analog
–
Reverse
Set Point>1200
100°
120
25