D8 Series User’s Guide
Chapter 4: Operation and Setup
64
For more information about alarms, see
and
Failed Sensor Alarm Messages
If the alarm is for a failed sensor, an alarm message appears in the first line of the loop display, as
shown in Figure 4.5.
Alarm Message
Alarm Code
01 T/C open
c
0
TO 1000man
h
0
Figure 4.5
– Display for Failed Sensor Alarm
Table 4.2 describes the alarm codes and messages for process alarms and failed sensor alarms.
Table 4.2
– Alarm Codes and Messages for Process and Failed Sensor Alarms
ALARM
CODE
ALARM MESSAGE
DESCRIPTION
AH
(No message)
Alarm high. Alarm High and Alarm Low on page 76
AL
(No message)
Alarm low. Alarm High and Alarm Low on page 76
HD
(No message)
High deviation alarm. Deviation Alarms on page 76
LD
(No message)
Low deviation alarm. Deviation Alarms on page 76
AW
(No message)
Ambient Warning: The controller is within 5°C of its operating temperature
limits. Ambient Warning on page 138
TO
T/C open
Thermocouple open. Thermocouple Open Alarm on page 74
TR
T/C reversed
Thermocouple reversed. Thermocouple Reversed Alarm on page 74
TS
T/C shorted
Thermocouple shorted. Thermocouple Short Alarm on page 74
RO
RTD open
RTD open. RTD Open and RTD Fail Alarms on page 74
RF
RTD fail
RTD open or shorted. RTD Open and RTD Fail Alarms on page 74
For details about the condition that causes each alarm, Setting Up Alarms on page 73
How to Acknowledge an Alarm
To acknowledge a process alarm, failed sensor alarm or system alarm, press
x
. If there are
other loops with alarm conditions, the alarm display switches to the next loop that has an alarm.
Acknowledge all alarms to clear the global alarm digital output.