Heat/Cool Derivative
l
01 Heat de-
r
rivative
b
0 sec
Enter the derivative constant. A larger value yields greater derivative action.
Values:
0 to 255 seconds
Default:
0
DeviceNet™ Object:
Control (66 hex)
Heat/Cool Manual Reset
l
01 Heat manual
r
reset
b
0%
A process that uses only proportional control settles at a point above or below the set point; it never
reaches the set point. This is known as
offset
or
droop
. At this parameter, enter the power level
required to maintain set point to compensate for this offset.
Values:
0 to 100% (0 to 1000). Values in parentheses are for communications.
Default:
0% (0)
Decimal Placement for DeviceNet™:
Decimal Placement for Percentage Values on page 46
DeviceNet™ Object:
Control (66 hex)
Heat/Cool Filter
l
01 Heat filter
r
b
3 scans
Use this parameter to dampen the response of the heat or cool output. The output responds to a
change by going to approximately two-thirds of its final value within the specified number of scans. A
larger value results in a slower response to changes in the process variable.
Values:
0 (off) to 255
Default:
3
DeviceNet™ Object:
Control (66 hex)