D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
107
Input Menu
l
01 Input
r
Other menus
b
Use the
Input
menu to configure the process input:
• Input type
• Engineering units
• Scaling, calibration and filtering.
Input Type
l
01 Input type
r
b
J t/c
Choose the type of sensor that is connected to the analog input.
Values:
See Table 6.7.
Default:
J thermocouple
(1)
DeviceNet™ Object:
Input (64 hex)
Table 6.7
– Input Types and Ranges
DISPLAY
VALUE
DeviceNet™
VALUE
DESCRIPTION
INPUT RANGE
J t/c
1
Type J thermocouple
-350 to 1400°F (-212 to 760°C)
K t/c
2
Type K thermocouple
-450 to 2500° F (-268 to
1371°C)
T t/c
3
Type T thermocouple
-450 to 750°F (-268 to 399°C)
S t/c
4
Type S thermocouple
0 to 3200°F (-18 to 1760°C)
R t/c
5
Type R thermocouple
0 to 3210°F (-18 to 1766°C)
B t/c
6
Type B thermocouple
150 to 3200°F (66 to 1760°C)
E t/c
20
Type E thermocouple
-328 to 1448°F (-200 to 787°C)
RTD
8
RTD
-328.0 to 1150.0°F (-200.0 to
621.1°C)
process
0
Voltage or current signal, depending upon
the hardware configuration. Table 1.1 —
Ordering Options on page 16
.
User defined. Setting Up Process
Variable Retransmit on page
77
skip
10
Loop is not used for control, does not
report alarms, and is not shown on the
scanning display.
(none)