D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
109
Calibration Offset
l
01 Calibration
r
offset
b
0 ˚F
For a thermocouple or RTD input, enter the offset to correct for signal inaccuracy. A positive value
increases the reading and a negative value decreases it. Use an independent sensor or your own
calibration equipment to find the offset for your system.
Values:
See Table 6.9
Default:
0 or 0.0
Decimal Placement for DeviceNet™:
Decimal Placement for Numeric Values on page 46
DeviceNet™ Object:
Input (64 hex)
Table 6.9
– Calibration Offset Ranges
TYPE OF SENSOR
OFFSET RANGE
°F
°C
RTD
-300.0 to 300.0
-300.0 to 300.0
J Thermocouple
K Thermocouple
T Thermocouple
-300 to 300
-300 to 300
B Thermocouple
S Thermocouple
-300 to 76
-300 to 300
R Thermocouple
-300 to 66
-300 to 300
Reversed Thermocouple Detection
l
01 Reversed
r
T/C detect
b
on
Choose whether to enable polarity checking for thermocouples. If the controller detects a reversed
thermocouple, it activates an alarm and sets the loop to manual mode at the power level indicated
by the
Sensor fail heat output
or
Sensor fail cool output
parameter in the
Output
menu.
Values:
on
(1) or
off
(0). Values in parentheses are for communications
Default:
on
(1)
DeviceNet™ Object:
Input (64 hex)