Chapter 6: Menu and Parameter Reference
112
Decimal Placement for DeviceNet™:
Decimal Placement for Percentage Values on page 46
DeviceNet™ Object:
Input (64 hex)
Input Filter
l
01 Input
r
filter
b
3scans
Choose the amount of filtering to apply to the process variable before the value is displayed or used
in the control calculation. The input filter simulates a resistor-capacitor (RC) filter. Use it to keep the
process variable from varying unrealistically.
When enabled, the process variable responds to a step change by going to two-thirds of the actual
value within the specified number of scans. One scan is 0.17 seconds for a four-loop controller and
0.33 seconds for a eight-loop controller.
Values:
0 (off) to 255
Default:
3
DeviceNet™ Object:
Input (64 hex)
Control Menu
l
01 Control
r
Other menus
b
Use the
Control
menu to adjust heat and cool control parameters, including:
• Proportional band, integral and derivative
• Output filter
• Control hysteresis
The controller has separate PID and filter settings for heat and cool outputs. In this section, only the
heat screens are shown, but the explanations apply to both the heat and cool parameters.
If you have not set up a Series D8 controller before, or if you do not know which values to enter,
Chapter 5: Tuning and Control on page 87, which contains PID tuning constants and useful
starting values.