D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
115
Hysteresis
l
01 Hysteresis
r
b
5 ˚C
Specify how much the process variable must deviate from set point before the output can switch
between on and off (for on/off control) or switch between heating and cooling (for heat/cool control).
Values:
See Table 6.12 for values and decimal placement. For communications the value is always 0
to 5000, see Table 6.12 for implied decimal location.
Default:
See Table 6.12
DeviceNet™ Object:
Control (66 hex)
Table 6.12
– Values for the Control Hysteresis and Deviation Alarm Parameters
INPUT TYPE
DISPLAY FORMAT
VALUES
DEFAULT
Thermocouple
n/a
0 to 500
5
RTD
n/a
0 to 500.0
5.0
Proess
-999 to 3000
0 to 500
5
-9999 to 30000
0 to 5000
50
-999.9 to 3000.0
0.0 to 500.0
5.0
-99.99 to 300.00
0.00 to 50.00
0.50
-9.999 to 30.000
0.000 to 5.000
0.050
-0.9999 to 3.0000
0.0000 to 0.5000
0.0050
Restore Automatic Mode
l
01 RestoreAuto
r
b
disabled
Choose a digital input. If the input is connected to controller common, the loop returns to automatic
control mode after a failed sensor is repaired (if it was in automatic mode when the sensor failure
occurred).
Values:
enabled by D/I1
to
enabled by D/I8
(1 to 8) or
disabled
(0). Values in parentheses are for
communications.
Default:
disabled
(0)
DeviceNet™ Object:
Control (66 hex)