D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
119
Decimal Placement for DeviceNet™
: Decimal Placement for Percentage Values on page 46
DeviceNet™ Object:
Output (65 hex)
Heat/Cool Power Limit Time
l
01 HtPwr limit
r
time
b
continuous
Enter the duration of the power limit set at the previous parameter, or choose
continuous
to keep the
limit in effect at all times.
If you choose a timed limit, the limit timer restarts whenever the controller powers up and whenever
the loop switches from manual to automatic mode.
Values:
1 to 999 minutes (1 to 999) or
continuous
(0). Values in parentheses are for
communications.
Default:
continuous
(0)
DeviceNet™ Object:
Output (65 hex)
Sensor Fail Heat/Cool Output
l
01 Sensor fail
r
heat output
b
0%
A loop will switch to manual mode at the specified output power if one of the following conditions
occurs while in automatic mode:
• A failed sensor alarm occurs, or
• The mode override input becomes active. Mode on page 96
• DeviceNet™ connection becomes inactive unexpectedly.
For most applications, this parameter should be set to 0% for both heat and cool outputs.
Values:
0 to 100% (0 to 1000). Values in parentheses are for communications.
Default:
0% (0)
Decimal Placement for DeviceNet™:
Decimal Placement for Percentage Values on page 46
DeviceNet™ Object:
Output (65 hex)
WARNING!
Do not rely solely on the failed sensor alarm to adjust the output in the
event of a sensor failure. If the loop is in manual mode when a failed sensor alarm
occurs, the output is not adjusted. Install independent external safety devices to shut
down the system if a failure occurs.