D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
125
Alarm Low Function
l
01 Alarm low
r
func
b
off
Choose whether the alarm functions as an alarm or as a boost output, or disable the alarm.
Values:
See Table 6.14 .
Default:
off
DeviceNet™ Object:
See Alarm Acknowledge on page 133 and Alarm Function on page 134.
Alarm Low Output
l
01 Alarm low
r
output
b
none
Choose a digital output to activate when the low alarm occurs. You cannot choose an output that is
in use for closed-loop control or for the Serial DAC clock.
Values:
none
(0) or output 1 to 18 (1 to 18). Values in parentheses are for communications.
Default:
none
(0)
DeviceNet™ Object:
Alarm (67 hex)
Alarm Hysteresis
l
01 Alarm hys-
r
teresis
b
2 ˚C
Enter the amount by which the process variable must return within the alarm limit before a high
alarm, low alarm or deviation alarm clears. Use the alarm hysteresis to prevent repeated alarms as
the process variable cycles around an alarm limit.
Values:
See Table 6.15 on the following page for values and decimal placement. For
communications the value is always 0 to 5000.
Default:
See Table 6.15.
DeviceNet™
Alarm (67 hex)