D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
105
Digital Output Alarm Polarity
l
D/O alarm
r
polarity
b
on
Choose the polarity of all digital outputs used for alarms. This setting does
not
apply to the global
alarm output or the CPU watchdog output.
Values:
See Table 6.6.
Default:
on
(0)
DeviceNet™ Object:
Global (6B hex)
Table 6.6
– Digital Output Alarm Polarity
DISPLAY
VALUE
DeviceNet™
VALUE
DESCRIPTION
on
0
Digital alarm outputs sink current to analog common when an alarm
occurs.
off
1
Digital alarm outputs stop sinking current to analog common when an
alarm occurs.
MAC ID
l
MAC ID
r
b
63
The node address for the controller. This value is set with the Address rotary switches. Connecting
the D8 to a DeviceNet Network on page 41
Values:
00 to 63
DeviceNet™ Object:
DeviceNet™ (03 hex)
Baud Rate
l
Baud rate
r
b
500
Indicates the baud rate for communications. This value is set with the Data Rate rotary switch.
Connecting the D8 to a DeviceNet Network on page 41
Values:
125, 250, 500K
DeviceNet™ Object:
DeviceNet™ (03 hex)