D8 Series User’s Guide
Chapter 2: Installation
29
Table 2.2
–
Power Connections
FUNCTION
POWER SUPPLY
D8 J2
D8 TB2
DC Power (Controller)
+12 to 24VDC
J2-1
+
DC Common
12 to 24VDC Common
J2-2
–
Earth Ground
Ground
J2-3
1. Connect the dc common terminal on the power supply to the dc common (-) terminal on
D8 TB2 or pin 2 on J2.
2. Connect the positive terminal on the power supply to the dc positive (+) terminal on
D8 TB2 or pin 1 on J2.
3. If using an isolated dc output or another power supply to power the loads, connect the dc
common of the supply powering the loads to the dc common of the supply powering the
controller.
4. Use the ground connector on TB2 or pin 3 on J2 for chassis ground. This terminal is
connected to the CLS200 chassis and must be connected to earth ground.
5. Connect 120/240VAC power to the power supply.
NOTE!
Connect the dc common of the power supply used for loads to the dc common
of the supply powering the controller. If the supplies are not referenced to one another,
the controller’s outputs will not be able to switch the loads.
NOTE!
When making screw terminal connections, tighten to 4.5 to 5.4 inch-pound
(0.5 to 0.6Nm).
CAUTION!
Without proper grounding, the D8 may not operate properly or may be
damaged.
CAUTION!
To prevent damage from incorrect connections, do not turn on the ac power
before testing the connections as explained in See Testing the System on page 30.
NOTE!
Do not connect the controller’s dc common (COM) to earth ground. Doing so will
defeat the noise protection circuitry, making measurements less stable.