D8 Series User’s Guide
Chapter 2: Installation
36
All digital outputs sink current to controller common when on. The load may powered by the 5VDC
supplied by the controller at the TB50, or by an external power supply. When using an external
power supply, bear in mind:
• Connect the commons of the load supply and the controller power supply together near the
power supplies.
• Do not 24 volts.
• If you connect the external load to earth ground, or if you cannot connect it as shown in
Figure 2.17, then use a solid state relay.
The outputs conduct current when they are on. The maximum current sink capability is 60mA at
24VDC. The outputs cannot “source” current to a load.
Digital Output 1
Digital Output 2
Control Common
+5VDC
Loads
Digital Output 1
Digital Output 2
Do not connect
External
Power
+
-
TB50 or TB18
Loads
Supply
TB50 or TB18
to earth ground or
equipment ground
Figure 2.18
— Digital Output Wiring
Configuring Outputs
As you choose outputs for control and alarms, bear in mind the following points:
• You can enable or disable the control outputs. By default, heat outputs are enabled and cool
outputs are disabled.
• You can program each control output individually for on/ off, time proportioning, distributed
zero-crossing or Serial DAC control.
• You can individually program each control output for direct or reverse action.
• Alarm outputs other than the global alarm are non-latching. See Global Alarm on page 76.
• Alarms can be suppressed during process start up and for preprogrammed durations. See
Power Up Alarm Delay on page 103.
• Alarm outputs can be configured, as a group, to sink to output during an alarm or stop
current flow during an alarm. See Digital Output Alarm Polarity on page 105.