D8 Series User’s Guide
Chapter 2: Installation
43
baud rate switch was changed to 250k baud before the network power had been restored, the
controller will attempt to come back on the network at 250k baud.
NOTE!
When changing the baud rate via the software or by manually changing the switch
position, you will need to cycle power on the network for the change to take effect.
Node Address (MAC ID)
Valid node addresses on a DeviceNet™ network range from 0 to 63 decimal. When the switch is set
to the PGM position, the unit’s node address is determined by a software setting. If the switch is set
to “PGM” you must set the node address using the controller’s front panel or network-configuration
software. As long as the switch setting remains set for software selection, the controller will always
come back up on the network with the last software configured node address stored in the
controller’s memory.
Set the controller’s MAC ID with the two rotary switches on the side of the case. Set the most
significant digit (MSD) with the left switch and the least significant digit (LSD) with the right switch.
For example, to set the address to 23, set the MSD to 2 and the LSD to 3.
NOTE!
If the node address is changed with the switch, the D8 controller’s power must
be cycled before the change takes effect. If the node address is changed using software,
the change takes effect immediately.
Figure 2.26
– D8 Side with Rotary Switches
Status Indicators
The D8 controller has two indicator lights on the back, one labeled “NET” (Network) and the
other labeled “MOD” (Module). On power-up the controller performs a self-test. The indicator light
identified as “MOD” displays the result of this test as either pass (green) or fail (red). Also, under
normal operation the indicator lights indicate the health of the module and the network. In the
event that an indicator light should go from green to red either on power up or afterwards, consult
Table 2.11 and Table 2.12 below for basic troubleshooting.