D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
127
Heat/Cool Output Retransmit
l
01 Heat output
r
retrans PV
b
2
Choose the loop that provides the process variable to be retransmitted. For example, in the sample
display above, the heat output from loop 1 (01) will retransmit the process variable from loop 2.
Values:
none
(0), or loop 1 to 4 (1 to 4) for a four-loop controller or loop 1 to 8 (1 to 8) for an eight-
loop controller. Values in parentheses are for communications.
Default:
none
(0)
DeviceNet™ Object:
Retransmit (68 hex)
Heat/Cool Retransmit Low Process Variable
l
01 Ht retrans
r
LowPV
b
0 ˚C
Enter the value of the process variable to retransmit as a 0 percent output signal. If the process
variable falls below this value, the output will stay at 0 percent.
Values:
Any value within the input sensor range; see Table 6.7 – Input Types and Ranges on page
107.
Default:
The minimum value in the input sensor range
Decimal Placement for DeviceNet™:
See
Decimal Placement for Numeric Values on page 46.
DeviceNet™ Object:
Retransmit (68 hex)
Heat/Cool Retransmit High Process Variable
l
01 Ht retrans
r
HighPV
b
0 ˚C
Enter the value of the process variable to retransmit as a 100 percent output signal. If the process
variable rises above this value, the output will stay at 100 percent.
Values:
Any value within the input sensor range; see Table 6.7 – Input Types and Ranges on page
107.
Default:
The maximum value in the input sensor range
Decimal Placement for DeviceNet™
: See
Decimal Placement for Numeric Values on page 46.
DeviceNet™ Object:
Retransmit (68 hex).