D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
128
Cascade Menu
l
01 Cascade
r
Other menus
b
Use the cascade menu to configure cascade control. Use cascade control to calculate the
set point of the current loop (the secondary, or outer, loop) based upon the output of another loop
(the primary, or inner, loop).
For more information about cascade control, see Setting Up Cascade Control on page 79.
Cascade Primary Loop
l
01 Cascade
r
prim loop
b
none
Choose the primary loop. The controller uses the output of the primary loop to calculate the set point
of the current loop.
Values:
none
(0), or loop 1 to 4 (1 to 4) for a four loop-controller or 1 to 8 (1 to 8) for an eight-loop
controller. You cannot choose the current loop. Values in parentheses are for communications.
Default:
none
(0)
DeviceNet™ Object:
Cascade (6A hex)
Cascade Low Set Point
l
01 Cascade low
r
SP
b
25 ˚C
Enter the set point to use for the current loop when the output of the primary loop is at its minimum
value. The set point will never drop below this value.
• If the primary loop has only the heat output enabled, then this value is the set point when the
heat output of the primary loop is 0 percent.
• If the primary loop has only the cool output enabled or has the heat and cool outputs
enabled, then this value is the set point when the cool output is 100 percent.
Values:
For a thermocouple or RTD input, any value within the input range (see Table 6.7 ). For a
process input, any value between the
Input range low
and
Input range high
parameters. This value
must be less than the
Cascade hi SP
parameter.
Default:
25 for a thermocouple, RTD or process input.
Decimal Placement for DeviceNet™:
See Decimal Placement for Numeric Values on page 46.
DeviceNet™ Object:
Cascade (6A hex)