D8 Series User’s Guide
Chapter 4: Operation and Setup
86
Remote Analog Set Point Example: Changing a Set Point with a PLC
A PLC provides a 0 to 5VDC signal representing 0 to 300°F as a remote set point input to the D8.
The input signal is received on loop 1, and control is performed on loop 2. The D8 is equipped with
the proper scaling resistors to allow it to accept a 0 to 5VDC input.
Table 4.13 and Table 4.14 show the parameter settings for this application.
Table 4.13
– Parameters Settings for the Master Loop (Loop 1) in the Example
MENU
PARAMETER
VALUE
COMMENT
Input
Input type
process
A 0 to 5VDC input signal is a process input.
Input
Input range high
300.0° F
The 5VDC input signal represents 300°F.
Input
Input high signal
100.0%
The controller is equipped with a 0 to 5VDC
input, and the input signal is 0 to 5VDC,
so the signal covers the full scale of 0 to
100 percent.
Input
Input range low
0° F
The 0VDC input signal represents 0° F.
Input
Input low signal
0.0%
The controller is equipped with a 0 to 5VDC
input, and the input signal is 0 to 5VDC,
so the signal covers the full scale of 0 to
100 percent.
Table 4.14
– Parameter Settings for the Ratio Loop (Loop 2) in the Example
MENU
PARAMETER
VALUE
COMMENT
Ratio
Ratio master loop
01
Loop 1 is the master loop (receives the input
signal from the external device).
Ratio
Ratio low SP
0° F
For this example, we will assume that the
process can be set safely over the entire
range of 0 to 300°F. If desired, we could set a
more restrictive range for the ratio loop.
Ratio
Ratio high SP
300.0° F
Ratio
Control ratio
1.0
For this example, we want to retain the
original input value, so we will multiply it
times 1.0.
Input
Ratio SP diff
0
For this example, we want to retain the
original value, so we will add 0.
To complete the setup, loop 2 must be configured for inputs, outputs, and alarms. In addition, loop 1
may be configured for outputs and alarms.