D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
102
Mode Override
l
Mode override
r
b
disabled
Choose the digital input to use for the mode override feature. When the input is activated, the
controller sets all loops to manual mode at the output levels specified at the
Sensor fail heat output
and
Sensor fail cool output
parameters in the
Output
menu.
Use the
Mode override D/I active
parameter to choose which signal state activates the mode
override feature.
Values:
enabled by D/I1
to
enabled by D/I8
(1 to 8) or
disabled
(0). Values in parentheses are for
communications.
Default:
disabled
(0)
DeviceNet™ Object:
Global (6B hex)
WARNING!
Do not rely solely on the mode override feature to shut down your process.
Install external safety devices or overtemperature devices for emergency shutdowns.
Mode Override Digital Input Active
l
Mode override
r
D/I active
b
on
Choose whether the on state (connected to controller common) or off state (open circuit) activates
the mode override feature.
Use the
Mode override
parameter to enable the mode override feature and select the digital input.
Values:
on
(0) or
off
(1). Values in parentheses are for communications.
Default:
on
(0)
DeviceNet™ Object:
Global (6B hex)