D8 Series User’s Guide
Chapter 7: Troubleshooting and Reconfiguring
139
SYMPTOM
POSSIBLE CAUSES
RECOMMENDED ACTION
D8 display is lit, but
keys do not work
Keypad locked
See Keys Do Not Work on page 142.
Unacknowledged alarm
An alarm condition exists and has not been
acknowledged. See How to Acknowledge an Alarm on
page 64.
D8 damaged or failed
Return the D8 for repair. See Return Material
Authorization (RMA) on page 3.
Control mode
of one or more
loops changes
from automatic to
manual
Failed sensor
Check the display or HMI software for a failed sensor
message.
BCD job selection feature
loaded a different job
Check whether the new job was supposed to be
loaded. If not, check the BCD job load setup:
Check the settings of the BCD job load parameters in
the
Global setup
menu.
Use the
Digital inputs
parameter in the
I/O tests
menu
to test the BCD job load input(s).
Check the device that is used to activate job selection.
All loops are in
manual mode at 0
percent power
Intermittent power
Check wiring and service. See Wiring the Power
Supply on page 28.
Use a separate dc supply for the controller.
Provide backup power (uninterruptible power system).
In the Global menu, set the Power up loop mode
parameter to from memory if safe for your application.
See Power Up Loop Mode on page 103.
Hardware failure
Check the controller display for a hardware alarm. See
System Alarms on page 138.
Controller does
not behave as
expected
Corrupt or incorrect values
in RAM
Clear the RAM. See Clearing the RAM on page 145.
Reading the DeviceNet Indicator Lights
The Module Status Indicator Light indicates whether or not the device has power and is operating
properly. The following chart is the definition of valid states available to this indicator:
Table 7.3
– Module Status Indicator States and Descriptions
DEVICE STATE
INDICATOR LIGHT STATE
DESCRIPTION
Power Off
Off
No power applied to device.
Device Self-Test
Flashing Green-Red
Device is in Self-Test.
Device Operational
Green
Device is operating normally.
Unrecoverable Fault
Red
Device has detected an unrecoverable fault. All
module level faults are considred unrecoverable.
Содержание Controller Series D8
Страница 1: ...D8 Series User s Guide...
Страница 152: ...D8 Series User s Guide Chapter 7 Troubleshooting and Reconfiguring 152...
Страница 178: ...D8 Series User s Guide 178 Declaration of Conformity...