D8 Series User’s Guide
Chapter 7: Troubleshooting and Reconfiguring
138
Ambient Warning
The Ambient Warning indicates that the controller is within 5°C of its operating temperature limits. If
an Ambient Warning occurs, the alarm code AW (flashing) is displayed, and the global alarm output
is turned on. Acknowledging the alarm turns off the global alarm output. The error clears when the
condition no longer exists and the alarm has been acknowledged.
If the controller displays the AW alarm code:
1. Acknowledge the alarm.
2. Adjust the ambient temperature to a more appropriate level.
Failed Sensor Alarms
When a failed sensor alarm occurs, the controller switches to the single loop display for the loop with
the alarm and displays an alarm code (see Alarm Displays on page 63).
A failed sensor alarm clears once it has been acknowledged and the sensor is repaired. For more
information about the causes of failed sensor alarms, see Failed Sensor Alarms on page 73.
System Alarms
If the controller detects a hardware problem, it displays an alarm message, and with the exception
of the Low Power alarm, turns on the global alarm output. The global alarm remains on until the
alarm is acknowledged. The message persists until the condition is corrected and the alarm is
acknowledged.
The D8 displays the following system alarm messages:
•
Low power:
•
Battery dead:
•
H/W error: Ambient:
See H/W Error: Ambient on page 141.
•
H/W error: Gain:
See H/W Error: Gain or Offset on page 141.
•
H/W error: Offset:
See H/W Error: Gain or Offset on page 141.
Other Behaviors
Table 7.2 indicates potential problems with the system or controller and recommends corrective
actions.
Table 7.2
– Other Symptoms
SYMPTOM
POSSIBLE CAUSES
RECOMMENDED ACTION
Indicated
termperature not
as expected
Controller not
communicating
Sensor wiring inorrect
Noise
See Checking Analog Inputs on page 142.
D8 display is not lit
Power connection
incorrect
Check wiring and service. See Wiring the Power
Supply on page 28.
failed flash memory chip
Replace the flash memory chip. See Chapter 7:
Troubleshooting and Reconfiguring on page 136.
D8 damaged or failed
Return the D8 for repair. See Return Material
Authorization (RMA) on page 3.