The best way to avoid ground loops is to minimize unnecessary connections to ground. Do not
connect any of the following terminals to each other or to earth ground:
• Power supply dc common
• On J1 or TB1 any analog common
• J2 pin 2 or TB2 terminal 2 (DC power common)
Do not connect the analog common terminals to the other terminals listed above.
Power Connections
This section explains how to make power connections to the D8 and the TB50.
J1
Sensor Inputs
J2
Power Input
SCSI to TB50
Digital Inputs
Digital Outputs
Figure 2.11
– Power Input with Mass Termination Option
TB1
Sensor Inputs
TB2
Power Input
SCSI to TB50
Digital Inputs
Digital Outputs
Figure 2.12
– Power Input with Mass Termination Option
Wiring the Power Supply
WARNING!
Use a power supply with a Class 2 rating only. UL
®
approval requires a
Class 2 power supply.
Connect power to the controller before any other connections, This allows you to ensure that the
controller is working before any time is taken installing inputs and outputs.