D8 Series User’s Guide
Chapter 4: Operation and Setup
63
The control modes are described in Table 4.1
Table 4.1
– Control Modes
CONTROL MODE
DESCRIPTION
off
The loop is set to off. One or both outputs are enabled but
both outputs are at 0%.
man
The loop is in manual control. One or both outputs are
enabled.
auto
The loop is in automatic control. Only one output (heat or
cool) is enabled.
heat
The heat and cool outputs are enabled. The loop is in
automatic control and heating.
cool
The heat and cool outputs are enabled. Loop is in automatic
control and cooling.
tun
The loop is in autotune mode.
(blank)
The heat and cool outputs are both disabled.
NOTE!
If the input type for a loop is set to “skip,” the loop display will be blank for
that loop.
The scanning loop display sequentially displays the information for each loop. The data for each loop
displays for one second. To activate the scanning loop display, go to the loop display, then press and
hold the + side of the
p
key for three seconds. To exit the scanning mode, press any key.
Alarm Displays
If an alarm condition occurs, the controller displays an alarm code or alarm message.
Two-Character Alarm Codes
If a process, deviation, ambient warning or failed sensor alarm occurs, a two-character alarm code
appears in the lower left corner of the loop display.
The alarm code blinks and you cannot change the display until the alarm has been acknowledged.
After the alarm is acknowledged, the alarm code stops blinking. The alarm code remains on the
display until the condition that caused the alarm is corrected.
Alarm Code
01
925 ˚C
c
0
TO 1000man
h
100
Figure 4.4
– Loop Display with Alarm Code