D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
120
Open Thermocouple Heat/Cool Output Average
l
01 Open T/C ht
r
out average
b
off
If you set this parameter to
on
and a thermocouple open alarm occurs, a loop set to automatic
control mode will switch to manual mode at the average output prior to the alarm.
Values:
on
(1) or
off
(0). Values in parentheses are for communications.
DeviceNet™ Object:
Output (65 hex)
Heat/Cool Output Curve
l
01 Heat output
r
curve
b
linear
Choose an output curve. If curve 1 or 2 is selected, a PID calculation results in a lower actual output
level than the linear output requires. Use curve 1 or 2 if the system has a nonlinear response to the
output device.
Values:
linear
(0), curve 1 (1) or curve 2 (2). Values in parentheses are for communications.
Default:
linear
(0)
DeviceNet™ Object:
Output (65 hex)
Actual Output
0
20
40
60
80
100
10
20
30
40
50
60
70
80
90
3
8
13
27
48
62
2
4
7
12
29
44
66
Linear
Curve 1
Curve 2
36
19
19
79
Figure 6.3
– Linear and Nonlinear Outputs