D8 Series User’s Guide
Chapter 4: Operation and Setup
71
Table 4.4
– Input Readings
PROCESS VARIABLE
DISPLAYED
SENSOR INPUT
READING IN PERCENT
OF FULL SCALE
50.0 PSI
20mA
100%
.0 PSI
4mA
100% x (4mA/20mA) = 20%
Table 4.5
– Scaling Values
PARAMETER
VALUE
Input range high
50.0 PSI
Input high signal
100.0%
Input range low
.0 PSI
Input low signal
20.0%
Input Scaling Example: 0 to 5VDC Sensor
Situation
A flow sensor connected to the controller measures the flow in a pipe. The sensor generates a 0 to
5VDC signal. Independent calibration measurements of the flow in the pipe indicate that the sensor
generates 0.5V at 3 gallons per minute (GPM) and 4.75V at 65 GPM. The calibration instrument is
accurate ±1 GPM.
Setup
For the
Disp format
parameter in the
Input
menu, choose
-999to 3000
, because the calibrating
instrument is precise to ±1 GPM.
Table 4.6 and Table 4.7 show the minimum and maximum input signals and their corresponding
process variables, and the resulting values for the scaling parameters.
Table 4.6
– Input Readings and Calculations
PROCESS VARIABLE
DISPLAYED
SENSOR INPUT
READING IN PERCENT
OF FULL SCALE
65 GPM
4.75V
(4.75V / 5.00V) x 100% = 95%
3 GPM
0.5V
(0.5V / 5.00V) x 100% = 10%