D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
113
Heat/Cool Proportional Band
l
01 Heat prop
r
band
b
40 ˚F
Enter the proportional band. A larger value yields less proportional action for a given deviation from
set point.
Values:
For a thermocouple or RTD input, see Table 6.11. For a process input, 1 to the span of the
input range (
Input range high - Input range low
).
Default:
50 for a thermocouple, RTD or process input.
Decimal Placement for DeviceNet™:
Decimal Placement for Numeric Values on page 46
DeviceNet™ Object:
Control (66 hex)
Table 6.11
– Proportional Band Values
TYPE OF SENSOR
VALUES IN °F
VALUES IN °C
J Thermocouple
1 to 1750
1 to 972
K Thermocouple
1 to 2950
1 to 1639
T Thermocouple
1 to 1200
1 to 667
S Thermocouple
1 to 3200
1 to 1778
R Thermocouple
1 to 3210
1 to 1784
B Thermocouple
1 to 3350
1 to 1694
E Thermocouple
1 to 1776
1 to 987
RTD
0.1 to 1478.0
0.1 to 821.1
Heat/Cool Integral
l
01 Heat inte-
r
gral
b
180 sec/R
Enter the integral constant. A larger value yields less integral action.
Values:
0 (off) to 6000 seconds per repeat
Default:
For the
Heat integral
parameter, 180. For the
Cool integral
parameter, 60.
DeviceNet™ Object:
Control (66 hex)