D8 Series User’s Guide
Chapter 2: Installation
42
Connector Pinout
1
2
3
4
5
Figure 2.25
– J4 DeviceNet™ Connector Pinout
Table 2.9
–
DeviceNet™ Connector
PIN
SIGNAL
FUNCTION
1
Shield
Shield interconnect
2
V+
DeviceNet™ power
3
V-
DeviceNet™ power return
4
CAN+
Positive side of the DeviceNet™ bus
5
CAN-
Negative side of the DeviceNet™ bus
Network Length
The network speed is limited by the end-to-end network distance. The longer the network, the
slower the baud rate setting must be. See Table 2.10 below.
Table 2.10
–
Maximum Network Speed
DISTANCE
BAUD RATE
100 m (328 ft)
500 Kbps
250 m (820 ft)
250 Kbps
500 m (1,640 ft)
125 Kbps
Baud Rate (Data Rate)
DeviceNet™ communications can use three different baud rates (data rates) 125k, 250k, and
500k baud. When the switch is set to the PGM position, the unit’s baud rate is determined by a
software setting. If the switch is set to PGM you must set the data rate using the controller’s front
panel or network-configuration software. As long as the switch is set to PGM, the controller will
always come back up on the network with the last software-configured baud rate stored in the
controller’s memory.
As an example, assume the controller’s baud rate switch is set to PGM, and it is programmed at
500k baud. Assume too, that the DeviceNet™ network experiences a power loss. When power is
restored, the controller will come back up with a baud rate of 500k baud. If on the other hand, the