D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
96
Values:
For thermocouples and RTD inputs, same as the input range (see Table 6.7). For process
inputs, any value between the
Input range low
and
Input range high
parameters in the
Input
menu.
Default:
25
Decimal Placement for DeviceNet™:
Decimal Placement for Numeric Values on page 46
DeviceNet™ Object:
Assembly (04 hex), Input (64 hex)
Mode
l
01 Mode
r
b
manual
Choose the control mode for this loop.
Values:
See Table 6.1
Default:
off (3)
DeviceNet™ Object:
Assembly (04 hex), Control (66 hex)
Table 6.1
– Control Modes
DISPLAY
VALUE
DeviceNet™
VALUE
DESCRIPTION
manual
0
The operator manually sets the output power for the loop.
auto
1
The controller automatically controls the outputs according to the
controller configuration.
tune
2
The controller calculates PID parameters for the loop. After tuning, the
controller switches to automatic mode.
Off
3
Outputs are at 0%
Heat/Cool Output
l
01 Heat output
r
b
0%
Choose the manual output power level for this loop. This parameter is available only for the manual
control mode.
Values:
0 to 100% (0 to 1000). Values in parentheses are for communications.
Default:
0% (0)
Decimal Placement for DeviceNet™:
Decimal Placement for Percentage Values on page 46
DeviceNet™ Object:
Assembly (04 hex), Output (65 hex)