Setting range
00:10 to
100:00 h
Heating limit
<
T room (heating limit temperature)
The heating limit temperature defines the value of the outside temperature
below which central heating commences.
The heating limit temperature is the result of the selected set room temperature
less the value entered under "
Heating limit
<
T room
".
Example:
The selected set room temperature is 20 °C, the value entered under "
Heating
limit
<
T room
" is 4.0 K.
Central heating commences if the average outside temperature drops below
16 °C (heating limit temperature).
If the outside temperature exceeds 18 °C, central heating is adjusted because
of the specified hysteresis of 2 K.
A
Set room temperature
B
Outside temperature
C
Selected value "
Heating limit
<
T
room
"
D
Heating OFF
E
Heating ON
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Heating limit
<
T room"
(
1
/
!
)
Standard setting
4 K
Setting range
0 to 20 K
Average time; outside temperature
(cont.)
135
Control unit settings - system definition
55
92
968
GB
Service
Содержание VITOCAL 200-G
Страница 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Страница 65: ...Installing the heat pump module and making the cont 65 Installation sequence 5592 968 GB Installation ...
Страница 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Страница 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Страница 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Страница 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Страница 206: ...206 5592 968 GB ...
Страница 207: ...207 5592 968 GB ...