Setting the minimum heat pump runtime. The heat pump only switches off when
this time has elapsed.
This setting is designed to reach long heat pump runtimes to achieve high effi-
ciency and low wear.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heat pump
"
&
"Minimum runtime"
(
P
/
Q
)
Standard setting
2:00 min
Setting range
2:00 to 30:00
min
Min. compressor off
Setting the time that the compressor remains off before it can be restarted. This
protects the heat pump from overload conditions (3 starts per hour are the maxi-
mum).
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heat pump
"
&
"Min. compressor off"
(
P
/
Q
)
Standard setting
10:00 min
Setting range
00:20 to 30:00
min
Flow; primary/secondary pump
When the compressor starts, the following conditions must already be met:
&
The primary pump must already be running, to enable the primary circuit to cir-
culate brine.
&
The secondary pump must already be running, to enable the heat to be trans-
ferred immediately via the heating water.
Minimum runtime
139
Heat pump control settings
55
92
968
GB
Service
Содержание VITOCAL 200-G
Страница 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Страница 65: ...Installing the heat pump module and making the cont 65 Installation sequence 5592 968 GB Installation ...
Страница 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Страница 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Страница 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Страница 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Страница 206: ...206 5592 968 GB ...
Страница 207: ...207 5592 968 GB ...