A
Flow temperature
B
Differential between set room
temperature and outside tempera-
ture
C
Heating curve
D
Possible positive correction range
(0.1 to 10.0 K)
E
Possible negative correction
range
(0.1 to 10.0 K)
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Max. flow corr."
(
0
/
=
)
Standard setting
10.0 K
Setting range
0.1 to 10.0 K
Room temperature control
A room temperature-dependent control is possible subject to a room tempera-
ture sensor being installed and enabled. This function must be enabled for this.
Note
If "
Yes
" is selected for room control, the level and slope of the heating curve can
no longer be adjusted (weather-compensated control unit parameters).
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Room temperature control"
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Maximum flow temperature correction
(cont.)
159
Heating circuit control settings
55
92
968
GB
Service
Содержание VITOCAL 200-G
Страница 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Страница 65: ...Installing the heat pump module and making the cont 65 Installation sequence 5592 968 GB Installation ...
Страница 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Страница 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Страница 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Страница 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Страница 206: ...206 5592 968 GB ...
Страница 207: ...207 5592 968 GB ...