The reduced temperature mode (see operating instructions) will no longer be
used, if the outside temperature drops
below
this temperature limit. The equip-
ment heats up to the temperature selected for standard operation.
Operation will continue in accordance with the selected switching times, if the
average outside temperature stays
above
this temperature limit.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Temperature limit for red. BA"
(
1
/
!
)
Standard setting
-30 K
Setting range
-30 to +30 K
Frost protection temperature
The equipment enters reduced mode to protect itself against frost, as soon as
the average outside temperature drops below this value. This will be implemen-
ted independent of the setting of the operating mode selector.
The OFF point of the frost protection is set 2 K higher than the ON point.
A
Outside temperature
B
Frost protection temperature (can
be selected)
C
Frost protection OFF point (frost
protection tempe 2 K)
D
Reduced heating mode OFF
E
Reduced heating mode ON
Access
&
"
Device settings
"
&
"
Programming
"
&
"
System definition
"
&
"Frost protection T"
(
1
/
!
)
Standard setting
1 °C
Setting range
-15 to +15 °C
Temperature limit for reduced temperature mode
136
Control unit settings - system definition
55
92
968
GB
Содержание VITOCAL 200-G
Страница 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Страница 65: ...Installing the heat pump module and making the cont 65 Installation sequence 5592 968 GB Installation ...
Страница 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Страница 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Страница 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Страница 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Страница 206: ...206 5592 968 GB ...
Страница 207: ...207 5592 968 GB ...