Access
&
"
Device settings
"
&
"
Programming
"
&
"
Further menu items
"
&
"
Buffer cylinder
"
&
"Max. temperature"
(
1
/
!
)
Standard setting
60 °C
Setting range
1 to 70 °C
Stop optimisation
Note
This function is only available in case of
system design 2
, if the option "
Yes
"
was selected under "
Buffer cylinder
" (see page 169).
The stop optimisation ensures that, with the selected switching times (see oper-
ating instructions), the buffer cylinder is always fully heated at the end of stan-
dard mode.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Further menu items
"
&
"
Buffer cylinder
"
&
"Stop optimisation"
("
YES
"/"
NO
")
Standard setting
YES
Setting range
YES/NO
Excess reaction
Note
This function is only available in case of
system design 2
, if the option "
Yes
"
was selected under "
Buffer cylinder
" (see page 169).
Coordination of the heat drawn off in the secondary circuit when the heat pump
produces an excess of heat or the heat drawn by the secondary circuit is sud-
denly choked off.
Settings:
0
No heat drawn off
1
Heat will be drawn off only in case of a critical excess, i.e. if critical tem-
peratures were reached in the heat pump circuit or the minimum heat
pump runtime has not yet been reached.
Maximum temperature
(cont.)
171
Buffer cylinder control settings
55
92
968
GB
Service
Содержание VITOCAL 200-G
Страница 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Страница 65: ...Installing the heat pump module and making the cont 65 Installation sequence 5592 968 GB Installation ...
Страница 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Страница 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Страница 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Страница 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Страница 206: ...206 5592 968 GB ...
Страница 207: ...207 5592 968 GB ...