Note
This setting influences the natural cooling function. If the setting is
too low
, the
dew point monitor switches the cooling function off prematurely, subject to the
cooling curve (see page 155).
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Min. flow temp."
(
1
/
!
)
Standard setting
10 °C
Setting range
1 to 30 °C
DHW during party mode
This setting defines whether the DHW cylinder (setting "
Yes
") is heated first or
whether the system switches directly to heating mode (setting "
No
") when party
mode has been activated (see operating instructions).
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"DHW during party"
("
YES
"/"
NO
")
Standard setting
YES
Setting range
YES/NO
Excess reaction
Coordination of the heat drawn off in the secondary circuit when the heat pump
produces an excess of heat or the heat drawn by the secondary circuit is sud-
denly choked off.
Settings:
0
No heat drawn off
1
Heat will be drawn off only in case of a critical excess, i.e. if critical tem-
peratures were reached in the heat pump circuit or the minimum heat
pump runtime has not yet been reached
2
Heat will be drawn off, even if the excess heat being created is not critical
for the heat pump
Minimum flow temperature
(cont.)
156
Heating circuit control settings
55
92
968
GB
Содержание VITOCAL 200-G
Страница 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Страница 65: ...Installing the heat pump module and making the cont 65 Installation sequence 5592 968 GB Installation ...
Страница 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Страница 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Страница 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Страница 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Страница 206: ...206 5592 968 GB ...
Страница 207: ...207 5592 968 GB ...