background image

USER GUIDE

VOGUE COMBI GEN2

C26IE C32IE C40IE

When replacing any part on this appliance, use only spare parts that you can be 

assured conform to the safety and performance specification that we require.

Do not use reconditioned or copy parts that have  

not been clearly authorised by Ideal Boilers. 

 

July 2018     UIN 218172 A02 

Содержание 47-349-47

Страница 1: ...g any part on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers July 2018 UIN 218172 A02 ...

Страница 2: ...2 ...

Страница 3: ...troduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency Natural Gas only VOGUE COMBI IE GEN2 All Gas Safe Register installers carry a Gas Safe Register ID card and have a registration number Both should be recorded in the Benchmark Commissioning Che...

Страница 4: ...nterest and that of safety it is the law that this boiler must be installed by a Gas Safe Registered Engineer in accordance with the above regulations In IE the installation must be carried out by a Registered Gas Installer RGII and installed in accordance with the current edition of I S 813 Domestic Gas Installations the current Building Regulations and reference should be made to the current ETC...

Страница 5: ...ven supervision or instructions concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance In cases of repeated or continuous shutdown a Gas Safe Registered Engineer or in IE a Registered Gas Installer RGII should be called to investigate and rectify the condition causing this and carry out an operationa...

Страница 6: ...ication Legend BOILER CONTROLS 1 0 4 2 3 bar MENU READY TIMER OR ROOM THERMOSTAT OFF ON 60 C off max max boiler off D H F G A B C E D Hot Keys E Central Heating Temperature Control F Domestic Hot Water Temperature Control Off Switch G Pressure Gauge H Hot Key Identification Text ...

Страница 7: ...tral heating if required Note In normal operation the boiler colour screen will display the boiler operation mode Boiler frost protection boiler will fire if temperature is less than 5 degrees C During normal operation the burner on indicator C will remain illuminated when the burner is lit If the boiler has not lit after 5 ignition attempts the following screen will be displayed IGNITION LOCKOUT ...

Страница 8: ...mmobilised refer to page 20 This will stop the boiler operating periodically for short periods This facility is primarily provided for boiler installations in a sensitive area i e bedroom etc Note If the pump and diverter valve have not operated in the last 24 hours they will run briefly to ensure they do not become seized CONTROL OF WATER TEMPERATURE Domestic Hot Water The DHW temperature is limi...

Страница 9: ...emperature control knob F to between 40ºC 65ºC refer to colour screen whilst adjusting FROST PROTECTION If no frost protection is provided and frost is likely during a short absence from home leave the heating controls if fitted at a reduced temperature setting For longer periods the entire system should be drained If the system includes a frost thermostat then the timer can be left off if fitted ...

Страница 10: ...d Engineer or in IE a Registered Gas Installer RGII should be consulted THE BOILER WILL NOT OPERATE IF THE PRESSURE HAS REDUCED TO LESS THAN 0 5 BAR UNDER THIS CONDITION In this case the following display will appear EXIT PICTURE LOW WATER PRESSURE With boiler off system cold fill system to between 1 0 1 5 bar Press PICTURE to see how Bleed radiators then refill If fault persists contact Ideal 014...

Страница 11: ... end of filling loop is hand tight 4 Turn the Domestic Hot Water DHW Inlet A blue handle to the horizontal position 5 Ensuring no leaks are seen gradually turn the filling loop handle blue B to the horizontal position 6 Wait for the pressure gauge to reach 1 to 1 5 bar 7 Once pressure is reached turn valves A B back to the closed position 8 Disconnect the filling loop replace cap and plug Note the...

Страница 12: ...pe is frozen at the most exposed point external to the building or where there is some obstruction to flow This could be at the open end of the pipe at a bend or elbow or where there is a dip in the pipe in which condensate can collect The location of the blockage should be identified as closely as possible before taking further action 2 Apply a hot water bottle microwaveable heat pack or a warm d...

Страница 13: ...S LEAKS WITHANAKED FLAME CLEANING For normal cleaning simply dust with a dry cloth To remove stubborn marks and stains wipe with a damp cloth and finish off with a dry cloth DO NOT use abrasive cleaning materials MAINTENANCE The appliance should be serviced at least once a year by a Gas Safe Registered Engineer or in IE a Registered Gas Installer RGII ...

Страница 14: ...ough the following guide to identify any problems external to the boiler prior to requesting a service engineer s visit Should the problem be found to be other than with the appliance we reserve the right to levy a charge for the visit or for any pre arranged visit where access is not gained by the engineer ...

Страница 15: ...re that the timer and Room Stat are switched on Check batteries in programmable room stats Rotate the Domestic Hot Water temperature control knob F clockwise Note that in cold weather it may be necessary to restrict the flow from the tap to achieve the desired temperature Ensure that the mains supply to the boiler is switched on and that no trips have operated in the consumer unit Ensure that the ...

Страница 16: ...owers are off Indicates that the timer or room stat is switched off Indicates that Central Heating has been switched off at the boiler Rotate Central Heating knob clockwise to switch on at the boiler CENTRAL HEATING OFF MENU Indicates that the boiler is providing hot water at 60ºC MENU READY TIMER OR ROOM THERMOSTAT OFF ON 60 C MENU READY PREHEAT OFF READY TIMER OR ROOM THERMOSTAT OFF ...

Страница 17: ...icates that the boiler is pre heating To switch pre heat Off see page 20 Indicates that a Service is due To reset see page 22 Reset Service Time ON MENU READY PREHEAT ON 80 C MENU READY TIMER OR ROOM THERMOSTAT OFF SWITCH OFF TEMPERATURE AT 60O C PREHEAT ACTIVE MENU BOILER FROST PROTECTION ACTIVE SWITCH OFF TEMPERATURE 19O C MENU READY TIMER OR ROOM THERMOSTAT OFF SERVICE DUE Ideal Boilers 01482 4...

Страница 18: ...radiator temperature rotate the Central Heating knob E This screen will be shown To switch the heating off rotate the Central Heating knob E fully anti clockwise This screen will be shown EXIT 60O C 65 O C 40 O C OFF SELECT HOT WATER TEMPERATURE EXIT 60O C 80 O C 30 O C OFF SELECT MAXIMUM RADIATOR TEMPERATURE EXIT 60O C 80 O C 30 O C OFF SELECT MAXIMUM RADIATOR TEMPERATURE EXIT OFF 80 O C 30 O C O...

Страница 19: ...will be shown To change the room temperature set point only if outside sensor connected rotate the Central Heating knob E This screen will be shown To switch the boiler on rotate the Domestic Hot Water knob F This screen will be shown OFF MENU EXIT 60O C 65 O C 40 O C OFF SELECT HOT WATER TEMPERATURE EXIT 22O C 30 O C 10 O C OFF SELECT ROOM TEMPERATURE ...

Страница 20: ...OFF To switch preheat on press ON Press MENU and the following screen will be displayed Press MENU SHOW EFFICIENCY LEVEL HOT WATER PREHEAT ON OFF SERVICE COMPANY PHONE NUMBER SERVICE COMPANY NAME SELECT EXIT and press select EXIT SELECT MENU HOT WATER PREHEAT ON OFF SERVICE COMPANY NAME SHOW EFFICIENCY LEVEL EXIT SELECT MENU SERVICE COMPANY NAME SERVICE COMPANY PHONE NUMBER HOT WATER PREHEAT ON OF...

Страница 21: ...and the following screen will be displayed Press select and a screen similar to the following will be displayed Press EXIT twice to return to normal operation EXIT SELECT MENU HOT WATER PREHEAT ON OFF SERVICE COMPANY NAME SHOW EFFICIENCY LEVEL EXIT MIN MAX EFFICIENCY LEVEL 60 ...

Страница 22: ... until the following screen is displayed Press SELECT and the following screen is displayed Press MENU SHOW EFFICIENCY LEVEL HOT WATER PREHEAT ON OFF SERVICE COMPANY PHONE NUMBER SERVICE COMPANY NAME MAX OFF MAX OFF SELECT EXIT until the desired number of days required Press SET Press EXIT to return to normal operation EXIT SELECT MENU HOT WATER PREHEAT ON OFF SERVICE COMPANY NAME SHOW EFFICIENCY ...

Страница 23: ...23 ...

Страница 24: ...rmance of its products The right is therefore reserved to vary specification without notice Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal Consumer Helpline 01482 498660 www idealboilers com ...

Отзывы: