2.
Remove the front part of the heat
pump thermal insulation (see
page 63).
3.
Check the floor area, valves and all
visible solder joints for traces of oil.
Filling the primary circuit, venting it and checking its pres-
sure
!
Please note
To prevent equipment damage, it is
vital
to prevent the compressor from
being switched on if the primary circuit
has not been filled
.
For this, pull the plug-in connector from the compressor (see page 65).
1. Only for commissioning:
Flush the primary circuit.
2. Only for commissioning:
Fill the primary circuit with heat
transfer medium "Tyfocor -15 ° C"
and vent the circuit.
3.
Check the primary circuit pressure.
The pressure should be approx.
2 bar.
4.
Check the pre-charge pressure of
the diaphragm expansion vessel
and adjust if required (see
page 102).
Further details regarding the individual steps
(cont.)
100
Commissioning, inspection, maintenance
55
92
968
GB