![Veikong VFD700 Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/veikong/vfd700-series/vfd700-series_operation-manual_3864500009.webp)
1 Technical specification
2VFD700 AC Drive Getting Started Guide
Figure1-3 VFD700 rating label (
Double power type)
NOTE: Size A, B, C are single types. Size D and above are G/P types.
1.3 Power size
Power size of VFD700 is based on the standard 4 poles inductionmotor at rated voltage.
E, G: Heavy duty
P: Normal duty
Overload of E, G type: 150% rated output current, 1 minute
Overload of Ptype: 110% rated output current, 1 minute
Table 1-1 220V rating data
Power supply: 200VAC~240VAC, 50Hz/60Hz, single/three phase
Model
Default carrier
frequency (kHz)
Drive
Power Size
(kVA)
Rated Input
Current(A)
Rated
Output
Current(A)
MotorP
ower(k
W)
Size
1/3PH
VFD700-20D00040
6
1.1
7.1/4
2.8
0.4
A
VFD700-20D00075
6
1.9
12.8/7.1
5
0.75
A
VFD700-20D00150
6
3.0
20.5/11.3
8
1.5
A
VFD700-20D00220
6
4.2
24/14.5
11
2.2
B
VFD700-20D00400
6
6.7
30.4/16.5
17.6
4
C
Table 1-2380V rating data
Power supply: 380VAC~480VAC, 50Hz, three phase
Model
Default
carrier
freque-
ncy
(kHz)
G
P
Size
Drive
Power
Size
(kVA)
Rated
Input
Current
(A)
Rated
Output
Current
(A)
Motor
Power
(kW)
Drive
Power
Size
(kVA)
Rated
Input
Current
(A)
Rated
Output
Current
(A)
Motor
Power
(kW)
VFD700-40T00075
6
1.7
3.6
2.5
0.75
−
−
−
−
A
VFD700-40T00150
6
2.8
5.7
4.2
1.5
−
−
−
−
A
VFD700-40T00220
E
6
3.4
6.1
5.2
2.2
A
VFD700-40T00220
6
3.8
8.3
5.8
2.2
−
−
−
−
B
VFD700-40T00400
6
6.3
13.2
9.5
3.7
−
−
−
−
B
VFD700-40T00550
E
6
8.6
14.3
13
5.5
−
−
−
−
B
VFD700-40T00550P
6
−
−
−
−
8.6
14.3
13
5.5
B
VFD700-40T00550
6
8.6
12.4
13
5.5
−
−
−
−
C
VFD700-40T00750
6
11
16.1
17
7.5
−
−
−
−
C
VFD700-40T01100P
6
−
−
−
−
15.2
21
23
11
C
VFD700-40T01100
6
16.5
24
25
11
21
31
32
15
D
VFD700-40T01500
6
21
31
32
15
25
36
38
18.5
D