Appendix
VFD700 AC Drive Getting Started Guide
119
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P09.09
Status
relays
function
level
control
0: P09.10
~
P09.11 are
basic application (0
~
12)
1: P09.10
~
P09.11
advanced application
(P00.00
~
P18.08)
1
0
Run&Stop
038CH
P09.10
Relay1
function
0: Drive healthy
1: Drive is active
2: Length arrival
3: External trip
4: Under voltage trip
5: PLC finished
6: Frequency is arrival
7: Torque limit is working
8: Time arrival
9: Overload is calculating
10: At zero speed
11: Brake logic is on
12: No function
99*: Advanced function
1
Relay1: 0
Run&Stop
038DH
P09.11
Relay2
function
Relay2: 1
038EH
P09.12 DI1 inverter
0: Off
1: On
1
0
Run&Stop
038FH
P09.13 DI2 inverter
0: Off
1: On
1
0
Run&Stop
0390H
P09.14 DI3 inverter
0: Off
1: On
1
0
Run&Stop
0391H
P09.15 DI4 inverter
0: Off
1: On
1
0
Run&Stop
0392H
P09.16 DI5 inverter
0: Off
1: On
1
0
Run&Stop
0393H
P09.17 DI6 inverter
0: Off
1: On
1
0
Run&Stop
0394H