Appendix
116VFD700 AC Drive Getting Started Guide
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P08.14
Analogue
output
function select
0: Output frequency
1: Reference frequency
2: Active current
3: Output current
4: Motor speed
5: DC voltage
6: Output voltage
7: AI1 level
8: AI2 level
9: Length
10: Counting
11:No function
99*: Advanced function
1
0
Run&Stop
032DH
When AO1 select the following function and 100% output
0: Output frequency
Maximum running frequency
1: Reference frequency
Maximum running frequency
2: Active current
3 times motor rated current
3: Output current
3 times motor rated current
4: Motor speed
The motor speed (rpm) is calculated
according to the maximum frequency
5: DC voltage
220: 415V
400: 830V
690: 1125V
6: Output voltage
Motor rated voltage
7: AI1 level
10V
8: AI2 level
10V
9: Length
60000
10: Counting
60000
P08.15
Analogue
output scaling
0.000
~
20.000
0.001
1.000
Run&Stop
032EH