3 Operation and display
VFD700 AC Drive Getting Started Guide 57
When (P09.22=2) 3-wire control mode 2 is selected, DI1, DI2, DI3 are automatically set
as below:
P09.02=2
DI1 is "RUN" input, Latching control
P09.03=5
DI2 is 3-wire enable, Voltage control (SB1 is normal closed button, when
it is open, drive will stop)
P09.04=6
DI3 is FWD/REV input, Voltage control
Wiring is as figure 3-13:
HD700
DI1
DI2
DI3
SB1
SB2
K
0V(+24V)
Figure 3-13 3-wire control mode2 connection
SB1: Run button
SB2: Stop button
K: Direction switch
Press SB1, the drive will run, order is latched.
K is open, run forward; K is closed, run reverse.
Press SB2, the drive stops.
NOTE: After pressing SB2, the drive stops. Release the SB2 button and the drive still
stop. You have to trigger the SB1 againto make the drive run.