Appendix
114VFD700 AC Drive Getting Started Guide
Menu P08: Analogue input and output
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P08.01
Analogue
input function
level control
0: P08.03 and P08.08 are
only basic function (0
~
3)
1: P08.03 and P08.08 are
advanced application
(P00.00
~
P18.08)
1
0
Run&Stop
0320H
P08.02 AI1 mode
0: 0mA
~
20mA
1: 20mA
~
0mA
2: 4mA
~
20mA(current
loosing with trip)
3: 20mA
~
4mA(current
loosing with trip)
4: 4mA
~
20mA(current
loosing without trip)
5: 20mA
~
4mA(current
loosing without trip)
6: 0V
~
10V
1
6
Stop Only
0321H
P08.03
AI1 function
select
0: Analogue input1
1: Speed limit (Torque
control)
2: Torque offset
3: No function
99*: Advanced function
1
0
Stop Only
0322H
P08.04 AI11 offset
-
200.0%
~
+200.0%
0.1%
0.0%
Run&Stop
0323H
P08.05 AI1 scaling
0.000
~
20.000
0.001
1.000
Run&Stop
0324H
P08.06 AI1 inverter
0: Off
1: On
1
0
Run&Stop
0325H
P08.07
AI1 filtering
time
0.00s
~
10.00s
0.01s
0.1s
Run&Stop
0326H