Appendix
VFD700 AC Drive Getting Started Guide
115
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P08.08
AI2 function
select
0: Analogue input2
1: Speed limit (Torque
control)
2: Torque offset
3: No function
99*: Advanced function
1
0
Stop Only
0327H
P08.09 AI2 offset
-
200.0%
~
+200.0%
0.1%
0.0%
Run&Stop
0328H
P08.10 AI2 scaling
0.000
~
20.000
0.001
1.000
Run&Stop
0329H
P08.11 AI2 inverter
0: Off
1: On
1
0
Run&Stop
032AH
P08.12
AI2 filtering
time
0.00s
~
10.00s
0.01s
0.1s
Run&Stop
032BH
P08.13
Analogue
output
function level
control
0: P08.14 is only basic
application (0
~
11)
1: P08.14 is advanced
application (P00.00
~
P18.08)
1
0
Run&Stop
032CH