4 Parameters
60VFD700 AC Drive Getting Started Guide
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.03 (P10.07)
Control Mode
0
~
2
【
0
】
Stop Only
0: Keypad control
1: Terminal control
2: Serial comms. control
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.04 (P01.01)
Reference source
0
~
8
【
0
】
Run&Stop
0: Keypad
Using the
▲
or
▼
keys the frequency reference can be changed, and the power up
frequency reference is decided by parameter P00.12 (P01.11).
1: UP/DOWN
Through the two terminals which are defined as UP, DOWN functionthe reference can be
changed.
For example:
Define the DI4 and DI5 as UP and DOWN respectively, and the setup is as below:
P09.05=8
DI4 function is UP
P09.06=9
DI5 function is DOWN
2: Preset
Controlled by the digit input terminals, the frequency reference is the value of P04.01 (preset
1)
~
P04.16 (preset 16).
Use the default setup as an example:
P09.05=0
DI4 is preset select bit 0
P09.06=1
DI5 is preset select bit 1
There are two operation modes:
When the reference source is preset, terminal status is as shown below:
Table 4-1 Preset and preset terminal status corresponding table 1
DI5 Status (bit 1)
DI4 Status (bit 0)
Speed
OFF
OFF
Preset1 (P04.01)
OFF
ON
Preset2 (P04.02)
ON
OFF
Preset3 (P04.03)
ON
ON
Preset4 (P04.04)