![Veikong VFD700 Series Скачать руководство пользователя страница 136](http://html1.mh-extra.com/html/veikong/vfd700-series/vfd700-series_operation-manual_3864500136.webp)
Appendix
VFD700 AC Drive Getting Started Guide
129
Menu P13: Motor
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P13.01
Motor voltage
control mode
0: V/F
1: Open loop vector
control 1
2
:
Open loop vector
control 2
1
0
Stop Only
0514H
P13.02
Auto-tune
0: Disabled
1: Auto-tune 1
(run a time)
2: Auto-tune 2
(run once a time)
3: Reserved
1
0
Stop Only
0515H
P13.03
Motor 1/ motor
2 select
0: Motor 1
1: Motor 2
1
0
Stop Only
0516H
P13.04
Reserved
−
−
−
−
−
P13.05
Motor 1 power
factor
0.00
~
1.00
0.01
0.85
Stop Only
0518H
P13.06
Motor 1 rated
voltage
200V: 0V
~
240V
400V: 0V
~
480V
690V: 0V
~
690V
1V
200V: 220V
400V: 380V
690V: 660V
Stop Only
0519H
P13.07
Motor 1 rated
current
G or P type:
0.1A
~
rated current
×
1.2
GP type:
0.1A
~
P type rated
current
0.1A
By model
Stop Only
051AH
P13.08
Motor 1 rated
frequency
1.00Hz
~
300.0Hz
0.01Hz
50.00Hz
Stop Only
051BH