![Veikong VFD700 Series Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/veikong/vfd700-series/vfd700-series_operation-manual_3864500035.webp)
2 Installation and cabling
28VFD700 AC Drive Getting Started Guide
Model
Fuse
Power
Control
cable
(mm
2
)
IEC gR
(A)
Ferraz HSJ
(A)
Input
current
(A)
Supply
cable
(mm
2
)
Motor
cable
(mm
2
)
VFD700-40T02200
80
80
58
16
16
≥0.5
VFD700-40T03000
E
110
110
72
25
25
≥0.5
VFD700-40T03700
E
125
125
93
25
25
≥0.5
VFD700-40T03000
110
110
72
25
25
≥0.5
VFD700-40T03700
125
125
93
25
25
≥0.5
VFD700-40T04500
200
175
121
35
35
≥0.5
VFD700-40T05500
250
225
151
70
70
≥0.5
VFD700-40T07500
250
225
175
95
95
≥0.5
VFD700-40T09000
250
250
204
120
120
≥0.5
VFD700-40T11000
315
300
248
150
150
≥0.5
VFD700-40T13200
350
400
301
185
185
≥0.5
VFD700-40T16000
E
450
500
340
120×2
120×2
≥0.5
VFD700-40T18500
E
500
500
375
120×2
120×2
≥0.5
VFD700-40T20000
E
500
500
415
120×2
120×2
≥0.5
VFD700-40T16000
450
500
340
120×2
120×2
≥0.5
VFD700-40T18500
500
500
375
120×2
120×2
≥0.5
VFD700-40T20000
630
600
457
120×2
120×2
≥0.5
VFD700-40T25000
670
−
505
150×2
150×2
≥0.5
VFD700-40T28000
700
−
592
150×2
150×2
≥0.5
VFD700-40T31500
700
−
653
150×3
150×3
≥0.5
VFD700-40T35500
1000
−
728
150×4
150×4
≥0.5
VFD700-40T31500
E
700
−
653
150
×
3
150
×
3
≥
0.5
VFD700-40T35500
E
1000
−
728
150
×
4
150
×
4
≥
0.5
VFD700-40T40000
1000
−
810
150×4
150×4
≥0.5
VFD700-40T45000
1000
−
915
150×4
150×4
≥0.5
VFD700-60T03000
63
60
42
10
10
≥0.5
VFD700-60T03700
80
60
52
16
16
≥0.5
VFD700-60T04500
100
90
61
16
16
≥0.5
VFD700-60T05500
125
100
83
25
25
≥0.5
VFD700-60T07500
125
125
97
35
35
≥0.5
VFD700-60T09000
200
175
127
50
50
≥0.5
VFD700-60T11000
250
225
145
70
70
≥0.5
VFD700-60T13200
250
225
145
70
70
≥0.5
VFD700-60T16000
E
250
225
170
50×2
50×2
≥0.5
VFD700-60T18500
E
250
250
192
50×2
50×2
≥0.5
VFD700-60T20000
E
315
300
224
70×2
70×2
≥0.5