130VFD700 AC Drive Getting Started Guide
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P13.09
Number of
motor 1 pairs
of pole
0: Auto
1: 2 pole
2: 4 pole
3: 6 pole
4: 8 pole
1
2
Stop Only
051CH
P13.10
Motor 1 rated
speed
1rpm
~
60000rpm
1rpm
0rpm
Stop Only
051DH
P13.11
Motor 1 stator
resistance
0.000Ω
~
60.000Ω
0.001Ω
0
Stop Only
051EH
P13.12
Reserved
−
−
−
−
−
P13.13
Motor 1
transient
inductance
0.00%
~
50.00%
0.01%
by model
Stop Only
0520H
P13.14
~
P13.16
Reserved
−
−
−
−
−
P13.17
Motor 2 power
factor
0.00
~
1.00
0.01
0.85
Stop Only
0524H
P13.18
Motor 2 rated
voltage
200V: 0V
~
240V
400V: 0V
~
480V
690V: 0V
~
690V
1V
200V: 220V
400V: 380V
690V: 660V
Stop Only
0525H
P13.19
Motor 2 rated
current
G or P type: 0.1A
~
rated current
×
1.2
GP type:
0.1A
~
P type rated
current
0.1A
by model
Stop Only
0526H
P13.20
Motor 2 rated
frequency
1.00Hz
~
300.0Hz
0.01Hz
50.00Hz
Stop Only
0527H