![Veikong VFD700 Series Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/veikong/vfd700-series/vfd700-series_operation-manual_3864500036.webp)
2 Installation and cabling
VFD700 AC Drive Getting Started Guide 29
Model
Fuse
Power
Control
cable
(mm
2
)
IEC gR
(A)
Ferraz HSJ
(A)
Input
current
(A)
Supply
cable
(mm
2
)
Motor
cable
(mm
2
)
VFD700-60T16000
250
250
192
50×2
50×2
≥0.5
VFD700-60T18500
315
300
224
50×2
50×2
≥0.5
VFD700-60T20000
350
350
266
70×2
70×2
≥0.5
VFD700-60T25000
350
400
285
90×2
90×2
≥0.5
VFD700-60T28000
350
400
318
120×2
120×2
≥0.5
VFD700-60T31500
500
500
375
120×2
120×2
≥0.5
VFD700-60T35500
500
500
413
120×2
120×2
≥0.5
VFD700-60T31500
E
500
500
375
120
×
2
120
×
2
≥
0.5
VFD700-60T35500
E
500
500
413
120
×
2
120
×
2
≥
0.5
VFD700-60T40000
630
600
468
120×2
120×2
≥0.5
VFD700-60T45000
670
−
529
150×2
150×2
≥0.5
Table 2-15Earth conductor cross sectional area
Power cable cross sectional area-S (mm
2
)
Earth conductor cross sectional area-Sp (mm
2
)
S≤16
S
16<S≤35
16
35<S
S
/
2
NOTE: The data in the table 2-12 is based on the fact that two conductors are made of the
same metal material; otherwise the value should be modified by the conductor factor between
different metal materials.