5 Troubleshooting
74VFD700 AC Drive Getting Started Guide
Table 5-2 Fault category
Type
Trips
Description
Fault where the drive
can be reset
automatically
F003
F003 (under voltage), the drive can be reset
automatically according to actual DC bus voltage
Fault where the drive
can not be reset
≥F030
Fault from interal failure (except external disturbance).
EEPROM reading&
writeing fault
F020
When the trip occurs, user can load default, and then
reset the drive.
Odinary trips
F001, F006
The drive can be reset 10s after trouble removal
Other trips
The drive can be reset 1s after trouble removal
NOTE:
F003 can be auto-reset, the under voltage threshold level and hysteresis is different with
different rated voltage level.
When F003 happens, drive starts to save the parameters.
Only when the drive is active will the trip F003be recorded in the fault tracking log.
Menu P11 is for trip tracking.