![Veikong VFD700 Series Скачать руководство пользователя страница 142](http://html1.mh-extra.com/html/veikong/vfd700-series/vfd700-series_operation-manual_3864500142.webp)
Appendix
VFD700 AC Drive Getting Started Guide
135
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P15.16 PID hold
0: Off
1: On
1
0
Run&Stop
05EBH
P15.17
P15.12, P15.13
range
0: (P15.13)
≤
(P15.22)
≤
(P15.12)
1:
-
(P15.12)
≤
(P15.22)
≤
(P15.12)
1
0
Run&Stop
05ECH
P15.18
Main reference
level
-
100.0%
~
+100.0%
0.1%
Actual
Actual
05EDH
P15.19
PID reference
level
−100.0%
~
+100.0%
0.1%
Actual
Actual
05EEH
P15.20
PID feedback
level
-
100.0%
~
+100.0%
0.1%
Actual
Actual
05EFH
P15.21 PID error level
-
100.0%
~
+100.0%
0.1%
Actual
Actual
05F0H
P15.22 PID output level
-
100.0%
~
+100.0%
0.1%
Actual
Actual
05F1H
P15.23
Sleep mode
enable
0: Off
1: On
1
0
Stop Only
05F2H
P15.24
Sleep channel
selector
P00.00
~
P18.08
0.01
P05.11
Stop Only
05F3H
P15.25 Sleep threshold
0.00Hz
~
P01.02
(P15.24
=
P05.11)
0.0%
~
100.0%
(P15.24
=
other)
0.01Hz
0.1%
0.00Hz
0.0%
Stop Only
05F4H
P15.26 Sleep delay time 0.0s
~
3000.0s
0.1s
30.0s
Stop Only
05F5H
P15.27 Wakeup mode
0: Off
1: On
1
1
Stop Only
05F6H
P15.28
Wekeup channel
selector
P00.00
~
P18.08
0.01
P15.20
Stop Only
05F7H
P15.29
Wakeup
threshold
0.0%
~
100.0%
0.1%
0.0%
Stop Only
05F8H
P15.30
Wakeup delay
time
0.0s
~
3000.0s
0.1s
0.0s
Stop Only
05F9H