![Veikong VFD700 Series Скачать руководство пользователя страница 130](http://html1.mh-extra.com/html/veikong/vfd700-series/vfd700-series_operation-manual_3864500130.webp)
Appendix
VFD700 AC Drive Getting Started Guide
123
Menu P10: Comms. and general function
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P10.01 Protocol
0: Modbus RTU
1: Reserved
1
0
Run&Stop
03E8H
P10.02 Address
0
~
247
1
1
Run&Stop
03E9H
P10.03 Baud rate
0: 2.4KBPS
1: 4.8KBPS
2: 9.6KBPS
3: 19.2KBPS
4: 38.4KBPS
5: 57.6KBPS
1
3
Run&Stop
03EAH
P10.04
Comms.
configuration
0: 8-1-N, RTU, without
checking
1: 8-2-N, RTU, without
checking
2: 8-1-0, RTU, with odd
bit checking
3: 8-1-E, RTU, with even
bit checking
1
1
Run&Stop
03EBH
P10.05
Response delay
time
0ms
~
250ms
1ms
2ms
Run&Stop
03ECH
P10.06 User Code
0
~
9999
1
0
Run&Stop
03EDH
P10.07 Control mode
0: Keypad
1: Control terminal
2: Serial communication
1
0
Stop Only
03EEH
P10.08 Load default
0: Off
1: Load default
1
0
Stop Only
03EFH
P10.09 Fan control
0: Under control
1: Forced running
1
0
Run&Stop
03F0H
P10.10
Switch
frequency
1kHz
~
15kHz
1kHz
By
model
Run&Stop
03F1H