4 Parameters
VFD700 AC Drive Getting Started Guide 61
When the reference source is not preset, terminal status is as shown below:
Table 4-2 Preset and preset terminal status corresponding table 2
DI5 Status (bit 1)
DI4 Status (bit 0)
Speed
OFF
OFF
Keep the frequency setting
OFF
ON
Preset2 (P04.02)
ON
OFF
Preset3 (P04.03)
ON
ON
Preset4 (P04.04)
About 16 presets (P04.01
~
P04.16) control, please refer to Menu P04.
3: AI1
There are two analogue input terminals: AI1, AI2.
In this User manual, only AI1 is introduced.
According to parameter P08.03, AI1 has three functions:
P08.03=0, AI1 is speed reference
P08.03=1, AI1 is the speed limit under Torque control mode
P08.03=2, AI1is the Torque error
About AI1signal mode, there are current mode and voltage mode, for details please refer to the
explanation of parameter P00.05 (P08.02).
4: AI2
AI2 function is decided by the parameter P08.08, it is same with AI1, and the default function
is frequency reference.
AI2 can only be set to voltage mode.
For AI2detailed setup please refer to Menu P08
5: Serial comms.
Under this mode, user can change the value of P04.01 (Preset 1) for the reference. For details
please refer to the appendix1.
6: DI7 Pulse input
When P09.24=2, DI7 function is input of reference channel (by input pulse)
For example:
The maximum frequency of input pulse (P09.27) is 20.0kHz, and actual input pulse is
10.0kHz.
The percentage of DI7 pulse input (P09.38) is 50.0%. Then the reference is:
Reference =DI7 input percentage (P09.38)
×
maximum reference (P00.07)
=50.0%
×
50.00Hz
=25.00Hz