2 Installation and cabling
VFD700 AC Drive Getting Started Guide 27
NOTE:
To know how to choose fuse and switch please refer to table 2-14.
When the contactor is used in power supply control ,it is not suggested to use the power
contactor to control the drive to RUN/STOP .
Under default carrier frequency, the maximum motor cable length is 100 meters.When
the motor cable is longer than 100m, output reactor is suggested to use.
For the sake of safety, the drive and motor must be earthed, and the earth resistance must
be less than 10Ω, and the cross-sectional area of earth conductor must meet the
requirements in table 2-15.
Table 2-14 Recommended fuse, power cable and control cable
Model
Fuse
Power
Control
cable
(mm
2
)
IEC gG
(A)
<30A
,
CC class
>30A
,
T class
(A)
Input
current
(A)
Supply
cable
(mm
2
)
Motor
cable
(mm
2
)
1PH
3PH
1PH
3PH
1/3PH
1PH
3PH
3PH
VFD700-20D00040
10
8
10
8
7.1/4
1.5
1.0
1.0
≥0.5
VFD700-20D00075
16
10
15
10
12.8/7.1
2.5
1.0
1.0
≥0.5
VFD700-20D00150
25
16
25
15
20.5/11.3
2.5
1.5
1.0
≥0.5
VFD700-20D00220
32
20
32
20
24/14.5
4.0
2.5
1.5
≥0.5
VFD700-20D00400
20
20
16.5
2.5
2.5
≥0.5
VFD700-40T00075
8
8
3.6
1.0
1.0
≥0.5
VFD700-40T00150
10
10
5.7
1.0
1.0
≥0.5
VFD700-40T00220
E
16
15
8.3
1.5
1.0
≥0.5
VFD700-40T00220
16
15
8.3
1.5
1.0
≥0.5
VFD700-40T00400
20
20
13.2
2.5
1.5
≥0.5
VFD700-40T00550
E
32
20
14.3
2.5
2.5
≥0.5
VFD700-40T00550P
32
20
14.3
2.5
2.5
≥0.5
VFD700-40T00550
20
20
12.4
2.5
2.5
≥0.5
VFD700-40T00750
25
25
16.1
2.5
2.5
≥0.5
VFD700-40T01100P
40
40
21
4.0
4.0
≥0.5
VFD700-40T01100
40
40
31
4.0
4.0
≥0.5
VFD700-40T01500
50
45
36
6.0
6.0
≥0.5
VFD700-40T01850
63
60
44
10
10
≥0.5